Data sheet

CPX-FB6 (195748) bus node
{{ $t('shop.all.artikelnummer') }}:
OT-FESTO022843
Example illustration
{{ $t('shop.display.artikel.eigenschaften_headline') }}
Dimensions W x L x H 50 mm x 107 mm x 50 mm,
(Incl. linking block)
Parameterising Systemparameter,
Failsafe-Reaktion,
Diagnoseverhalten,
Forcen von Kanälen,
Signal-Setup
Additional functions Start-up parameterisation in text via field bus,
System status can be shown from process dat,
Additional diagnosis interface for control panel,
- Acyclical data access via "PCP" channel,
Channel related diagnosis via fieldbus
Operating element DIL switch
Operating voltage range DC [V] 18 to 30
Intrinsic power input at operating voltage Type 200 mA
Nominal operating voltage DC [V] 24
Corrosion resistant class KBK 1 - low corrosion stress
Bearing temperature [°C] -20 to 70
Protection category IP65,
IP67
ambient temperature [°C] -5 to 50
Max. address volume outputs [Byte] 12
Max. address volume inputs [Byte] 12
Report Interbus
Housing material PC,
PA reinforced
Fieldbus interface 2 x Sub-D plug can be populated,
2x M12x1, 5 pin, B-coded,
Socket and plug Sub-D, 9 pin
Device specific diagnosis Unterspannung Module,
Diagnose-Speicher,
Kanal- und modulorientierte Diagnose
Baud rate 500, 2000 kBit/s
LED display bus specific RC: Remote bus check,
RD: Remote bus disable,
TR: Transmit/Receive,
OM: Bus active,
UL: Operating voltage
LED display product specific PL: Load supply,
SF: System error,
M: Modify, parameterisation,
PS: Electronics supply, sensor supply
Further information:
{{ $t('shop.all.gewicht') }} 170 g / pcs
{{ $t('shop.all.gtin') }} 4052568158217
{{ $t('shop.display.artikel.zollwarennummer') }} 85176200
{{ $t('shop.all.hersteller') }} Festo
Figure
Landefeld Druckluft und Hydraulik GmbH · Konrad-Zuse-Straße 1 · 34123 Kassel · Germany
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
Our products arid goods are generally only intended for industrial and commercial uses.
As of: 08.12.2025