Data sheet

SRAP-M-CA1-270-1-A-T2P20 (570527) Sensorbox
{{ $t('shop.all.artikelnummer') }}:
OT-FESTO036183
Example illustration
{{ $t('shop.display.artikel.eigenschaften_headline') }}
Design Angular
Based on standard VDI/VDE 3845 (NAMUR)
Permission RCM mark,
c UL us - Recognized (OL)
CE certificate (see declaration of conformity) to EU EMC directive
UKCA marking (see declaration of conformity) RoHs compliant
Material information Angle of rotation
Measurement principle Hall magnetic
ambient temperature [°C] -20 to 80
Analogue output 4 - 20 mA
Repeatability analogue output in ± ° [deg] 1
Short circuit resistance yes
Overload resistant Available
Operating voltage range DC [V] 15 to 30
Empty run current [mA] 12 to 20
Reverse polarity protection for all electrical connections
Electrical connection 9 pin,
Screw clamp,
Pluggable
Lockable conductor nominal cross-section [mm²] 2,5
Connectable nominal cross section conductor M20
Permitted cable diameter [mm] 5 to 13
Max. line length 30 m
installation position arbitrary
Housing material Aluminium wrought alloy
Setting options Teach-in,
teach-in via electrical connection
Settings range angle recording [deg] 0 to 270
Protection category IP65
Insulation voltage [V] 50
Surge voltage strength [kV] 0,8
Protection class III
Corrosion resistant class KBK 3 - severe corrosion stress
Degree of contamination 3
Further information:
{{ $t('shop.all.gewicht') }} 1,2 kg / pcs
{{ $t('shop.all.gtin') }} 4052568217242
{{ $t('shop.display.artikel.zollwarennummer') }} 85365019
{{ $t('shop.all.hersteller') }} Festo
Figure
Landefeld Druckluft und Hydraulik GmbH · Konrad-Zuse-Straße 1 · 34123 Kassel · Germany
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
Our products arid goods are generally only intended for industrial and commercial uses.