Data sheet

CPX-4DE (195752) Input module
{{ $t('shop.all.artikelnummer') }}:
OT-FESTO011213
Example illustration
{{ $t('shop.display.artikel.eigenschaften_headline') }}
Dimensions W x L x H 50 mm x 107 mm x 50 mm,
(Incl. linking block and connectors)
Diagnosis Kurzschluss/Überlast pro Kanal
Parameterising Eingangsentprellzeit,
Signalverlängerungszeit,
Überwachung Modul,
Verhalten nach Kurzschluss
LED displays 1 Sammeldiagnose,
4 Kanalstatus
Operating voltage range DC [V] 18 to 30
Intrinsic power input at operating voltage Type 15 mA
Nominal operating voltage DC [V] 24
Potential separation channel - internal bus no
Potential separation channel - channel no
Corrosion resistant class KBK (In integrated condition),
1 - low corrosion stress
Bearing temperature [°C] -20 to 70
Protection category Depends on connection block
ambient temperature [°C] -5 to 50
Housing material PC,
PA reinforced
Quantity inputs 4
Input debouncing time 3 ms (0.1 ms, 10 ms, 20 ms parameterisable)
Fuse (short circuit) Internal electronic fuse Per module
Max. cumulative current inputs per module [A] 0,7
Switch level Signal 0: <= 5 V,
Signal 1: >= 11 V
Characteristic curves inputs IEC1131-T2
Switching logic inputs PNP (Positive switching)
Further information:
{{ $t('shop.all.gewicht') }} 105 g / pcs
{{ $t('shop.all.gtin') }} 4052568007997
{{ $t('shop.display.artikel.zollwarennummer') }} 85389099
{{ $t('shop.all.hersteller') }} Festo
Figure
Landefeld Druckluft und Hydraulik GmbH · Konrad-Zuse-Straße 1 · 34123 Kassel · Germany
All data are to be understood as non-binding reference values! We do not assume liability for any data selection not confirmed in writing. Unless otherwise specified, pressure values refer to liquids from Group II at +20°C.
Our products arid goods are generally only intended for industrial and commercial uses.
As of: 13.12.2025