Dimensions W x L x H |
50 mm x 107 mm x 55 mm, (Incl. linking block and connectors)
|
Diagnosis |
Unterspannung, Kommunikation, Übertemperatur, Drahtbruch pro Kanal, Kurzschluss pro Kanal, Prozesswertfehler, Querschluss pro Kanal, Selbsttest, Überspannung
|
Operating element |
DIL switch
|
LED displays |
1 Failsafe-Protokoll aktiv, 1 Sammeldiagnose, 8 Kanaldiagnose, 8 Kanalstatus
|
Operating voltage range DC [V] |
20.4 to 28.8
|
Intrinsic power input at operating voltage |
Type 35 mA For electronics
|
Nominal operating voltage DC [V] |
24
|
Potential separation channel - channel |
no
|
Corrosion resistant class KBK |
(In integrated condition), 1 - low corrosion stress
|
Bearing temperature [°C] |
-20 to 70
|
Protection category |
Depends on connection block
|
ambient temperature [°C] |
-5 to 50
|
Max. address volume outputs [Byte] |
7
|
Max. address volume inputs [Byte] |
6
|
Max. line length |
200 m
|
Material information |
RoHs compliant
|
Quantity inputs |
8
|
Characteristic curves inputs |
to IEC 61131-2 type 2
|
Switching logic inputs |
PNP (Positive switching)
|
Safety function |
Safe recording and analysis of input conditions
|
Safety Integrity Level (SIL) |
Safe recording and analysis of input conditions according to EN62061 to SIL CL3, Safe recording and analysis of input conditions according to EN61508 to SIL3
|
Performance Level (PL) |
Safe recording and analysis of input conditions according to ISO13849 to Cat.4 and PL e
|
Max. cumulative currents per module [A] |
3
|
residual ripple |
2 Vss within voltage range
|
Permission |
c UL us - Recognized (OL)
|
CE certificate (see declaration of conformity) |
to EU machinery directive
|
Certified awarding point |
01/205/5444.00/15
|
Probability of Failure per Hour in [1/h]. |
1e-009
|