Permission |
RCM mark, c UL us - Listed (OL)
|
CE certificate (see declaration of conformity) |
acc. to EU-EMV Directive, acc. to EU-RoHS Directive
|
KC-mark |
KC-EMV
|
Material information |
RoHs compliant
|
Measured parameter |
flow, temperature
|
Flow direction |
P1 -> P2, Uni-directional
|
Measurement process |
temperature: PT1000, Flow: Vortex
|
Flow measurement range starting value [l/min] |
1,8
|
Flow measurement range end value [l/min] |
32
|
Operating pressure [bar] |
0 to 12
|
Information about operating pressure |
max. 12 bar at 40°C, max. 6 bar at 100°C
|
Operating medium |
Fluid media, Neutral liquids, Water
|
Information about operating and control medium |
Media compatibility to the media contacting materials must be guaranteed
|
Medium temperature [°C] |
0 to 90
|
ambient temperature [°C] |
0 to 50
|
Nominal temperature [°C] |
23
|
Accuracy flow value |
±2 %FS for flow <= 50 %FS, ± 3 % o.m.v. for flow >= 50 %FS
|
Accuracy temperature in ± °C [°C] |
2
|
Repeatability flow value |
< ±0.5 %FS for flow <= 50 %FS, < ±1 % o.m.v. for flow >= 50 %FS
|
Temperature coefficient clamp in ± %FS/K |
type ±0,05%FS/K
|
Control output |
2 x PNP or 2 x NPN switchable
|
Switch function |
Window comparator, Threshold comparator, Freely programmable
|
Switching element function |
Opener/closer switchable
|
Max. output current [mA] |
100
|
Analogue output |
0 - 10 V, 4 - 20 mA, 1 - 5 V
|
Flow characteristic curve starting value [l/min] |
0
|
Flow characteristic curve end value [l/min] |
32
|
Max. load resistance current output [Ohm] |
500
|
Min. load resistance voltage output [kOhm] |
15
|
Short circuit resistance |
yes
|
Overload resistant |
Available
|
Report |
IO-Link
|
IO-Link, report |
Device V 1.1
|
IO-Link, profile |
Smart sensor profile
|
IO-Link, function classes |
Teach channel, Diagnosis, Identification, Binary data channel (BDC), Process data variables (PDV)
|
IO-Link, communication mode |
COM2 (38.4 kBaud)
|
IO-Link, SIO mode support |
yes
|
IO-Link, port type |
A
|
IO-Link, process data width OUT |
0 Bytes
|
IO-Link, process data width IN |
3 Bytes
|
IO-Link, process data contents IN |
1 bit BDC (Volume monitoring), 14 bit PDV (Flow measurement), 2 bit BDC (Flow monitoring)
|
IO-Link, service data unit IN |
32 bit Volumenmesswert
|
IO-Link, minimum cycle time |
5 ms
|
IO-Link, data memory needed [Byte] |
500
|
Operating voltage range DC [V] |
18 to 30
|
Reverse polarity protection |
for all electrical connections
|
Electrical connection |
M12x1, 5 pin, Plug straight, A-coded
|
Max. line length |
30 m, 20 m For OK link operation
|
installation position |
arbitrary
|
Fluid connection |
female thread G3/4
|
Housing material |
PA reinforced
|
From medium contacting materials |
EPDM (perox.), ETFE, stainless steel, PA6T/6I reinforced
|
Presentable unit(s) |
US gal, US gal/min, cft, cft/min, l, l/h, l/min, m3, °C, °F
|
Protection category |
IP65
|
Corrosion resistant class KBK |
3 - severe corrosion stress
|