SFAW-100T-CS520-E-PNLK-PNVBA-# (8036886) Flow sensor

Numer artykułu:

OT-FESTO060517

554,80 € z VAT
Szt.
Właściwości
Per­mis­sion RCM mark,
c UL us - Li­sted (OL)
CE cer­ti­fi­ca­te (see dec­la­ra­tion of con­for­mi­ty) acc. to EU-​EMV Di­rec­ti­ve,
acc. to EU-​RoHS Di­rec­ti­ve
KC-​mark KC-​EMV
Ma­te­rial in­for­ma­tion RoHs com­pliant
Me­asu­red pa­ra­me­ter flow,
tem­pe­ra­tu­re
Flow di­rec­tion P1 -> P2,
Uni-​directional
Me­asu­re­ment pro­cess tem­pe­ra­tu­re: PT1000,
Flow: Vor­tex
Flow me­asu­re­ment range star­ting value [l/min] 5,0
Flow me­asu­re­ment range end value [l/min] 100
Ope­ra­ting pres­su­re [bar] 0 to 12
In­for­ma­tion about ope­ra­ting pres­su­re max. 12 bar at 40°C,
max. 6 bar at 100°C
Ope­ra­ting me­dium Fluid media,
Neu­tral liquids,
Water
In­for­ma­tion about ope­ra­ting and con­trol me­dium Media com­pa­ti­bi­li­ty to the media con­tac­ting ma­te­rials must be gu­aran­te­ed
Me­dium tem­pe­ra­tu­re [°C] 0 to 90
am­bient tem­pe­ra­tu­re [°C] 0 to 50
No­mi­nal tem­pe­ra­tu­re [°C] 23
Ac­cu­ra­cy flow value ±2 %FS for flow <= 50 %FS,
± 3 % o.m.v. for flow >= 50 %FS
Ac­cu­ra­cy tem­pe­ra­tu­re in ± °C [°C] 2
Re­pe­ata­bi­li­ty flow value < ±0.5 %FS for flow <= 50 %FS,
< ±1 % o.m.v. for flow >= 50 %FS
Tem­pe­ra­tu­re co­ef­fi­cient clamp in ± %FS/K type ±0,05%FS/K
Con­trol out­put 2 x PNP or 2 x NPN swit­cha­ble
Switch func­tion Win­dow com­pa­ra­tor,
Thre­shold com­pa­ra­tor,
Fre­ely pro­gram­ma­ble
Swit­ching ele­ment func­tion Ope­ner/clo­ser swit­cha­ble
Max. out­put cur­rent [mA] 100
Ana­lo­gue out­put 0 - 10 V,
4 - 20 mA,
1 - 5 V
Flow cha­rac­te­ri­stic curve star­ting value [l/min] 0
Flow cha­rac­te­ri­stic curve end value [l/min] 100
Max. load re­si­stan­ce cur­rent out­put [Ohm] 500
Min. load re­si­stan­ce vol­ta­ge out­put [kOhm] 15
Short cir­cu­it re­si­stan­ce yes
Over­lo­ad re­si­stant Ava­ila­ble
Re­port IO-​Link
IO-​Link, re­port De­vi­ce V 1.1
IO-​Link, pro­fi­le Smart sen­sor pro­fi­le
IO-​Link, func­tion clas­ses Teach chan­nel,
Dia­gno­sis,
Iden­ti­fi­ca­tion,
Bi­na­ry data chan­nel (BDC),
Pro­cess data va­ria­bles (PDV)
IO-​Link, com­mu­ni­ca­tion mode COM2 (38.4 kBaud)
IO-​Link, SIO mode sup­port yes
IO-​Link, port type A
IO-​Link, pro­cess data width OUT 0 Bytes
IO-​Link, pro­cess data width IN 5 Bytes
IO-​Link, pro­cess data con­tents IN 1 bit BDC (vo­lu­me mo­ni­to­ring),
14 bit PDV (flow me­asu­re­ment),
1 bit BDC (tem­pe­ra­tu­re mo­ni­to­ring),
14 bit PDV (tem­pe­ra­tu­re me­asu­re­ment),
2 bit BDC (flow me­asu­re­ment)
IO-​Link, se­rvi­ce data unit IN 32 bit Vo­lu­men­mes­swert
IO-​Link, mi­ni­mum cycle time 5 ms
IO-​Link, data me­mo­ry ne­eded [Byte] 500
Ope­ra­ting vol­ta­ge range DC [V] 18 to 30
Re­ver­se po­la­ri­ty pro­tec­tion for all elec­tri­cal con­nec­tions
Elec­tri­cal con­nec­tion M12x1,
5 pin,
Plug stra­ight,
A-​coded
Max. line length 30 m,
20 m For OK link ope­ra­tion
in­stal­la­tion po­si­tion ar­bi­tra­ry
Fluid con­nec­tion Ter­mi­nal con­nec­tion DIN 32676 DN20
Ho­using ma­te­rial PA re­in­for­ced
From me­dium con­tac­ting ma­te­rials EPDM (perox.),
ETFE,
sta­in­less steel,
PA6T/6I re­in­for­ced
Pre­sen­ta­ble unit(s) US gal,
US gal/min,
cft,
cft/min,
l,
l/h,
l/min,
m3,
°C,
°F
Pro­tec­tion ca­te­go­ry IP65
Cor­ro­sion re­si­stant class KBK 3 - se­ve­re cor­ro­sion stress
Tem­pe­ra­tu­re me­asu­re­ment range sta­ting value [°C] 0
Tem­pe­ra­tu­re me­asu­re­ment range end value [°C] 90
Tem­pe­ra­tu­re cha­rac­te­ri­stic curve star­ting value [°C] 0
Tem­pe­ra­tu­re cha­rac­te­ri­stic curve end value [°C] 100